Theoretical Analysis on Pollution Flashover Voltage Prediction Based on Leakage Current of Porcelain Insulator in Service
- DOI
- 10.2991/icibet.2013.272How to use a DOI?
- Abstract
In this paper, leakage current obtained by laboratory was derived to calculate the pollution flashover voltage of porcelain insulators. On this basis, this paper ana-lyzed the basic theory of prediction of pollution flashover based on leakage cur-rent monitored in service. At the same time, the calculation results and the test results of pollution flashover voltage were compared. The results showed that the difference of flashover voltage between calculation results and test results was less than 5%. It is proved that the calculation method for evaluating the flashover risk by monitoring the leakage current proposed in this paper was effec-tive.
- Copyright
- © 2013, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Lei Song AU - Fuzeng Zhang AU - Xidong Liang AU - Yifan Liao PY - 2013/03 DA - 2013/03 TI - Theoretical Analysis on Pollution Flashover Voltage Prediction Based on Leakage Current of Porcelain Insulator in Service BT - Proceedings of the 2013 International Conference on Information, Business and Education Technology (ICIBET 2013) PB - Atlantis Press SP - 1255 EP - 1258 SN - 1951-6851 UR - https://doi.org/10.2991/icibet.2013.272 DO - 10.2991/icibet.2013.272 ID - Song2013/03 ER -