Research on Automatic Control Strategy of Direct Air-cooling System for 660 MW Thermal Power Plants
Authors
Song Gao, Bo Gao, Xiangrong Meng
Corresponding Author
Song Gao
Available Online April 2015.
- DOI
- 10.2991/isrme-15.2015.173How to use a DOI?
- Keywords
- Direct Air-cooling System, Automatic control Strategy, 660MW Thermal Power Plants
- Abstract
This research focuses on automatic control strategy of direct air-cooling system for 660 MW thermal power plants. The aim of the controller is to maintain the backpressure in an adjustable range. The speed control policy takes the backpressure to the controllable range by adjusting the running fan speed, and the sequential control policy starts or shutoffs the pre specified fans when the backpressure is out of the normal range. An application of 660 MW power unit shows that the automatic control strategy has important significance for the safe and economic operation of generating units.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Song Gao AU - Bo Gao AU - Xiangrong Meng PY - 2015/04 DA - 2015/04 TI - Research on Automatic Control Strategy of Direct Air-cooling System for 660 MW Thermal Power Plants BT - Proceedings of the 2015 International Conference on Intelligent Systems Research and Mechatronics Engineering PB - Atlantis Press SP - 843 EP - 846 SN - 1951-6851 UR - https://doi.org/10.2991/isrme-15.2015.173 DO - 10.2991/isrme-15.2015.173 ID - Gao2015/04 ER -