Proceedings of the 2015 International Conference on Electrical, Automation and Mechanical Engineering

Green Corrosion Inhibitor in Central Air-conditioning Cooling Water

Authors
M.D. Li, B. Yang, J.M. Zhao, Y.T. Chen, S.X. Gu, C.L. Dai
Corresponding Author
M.D. Li
Available Online July 2015.
DOI
10.2991/eame-15.2015.2How to use a DOI?
Keywords
sodium tungstate; sodium molybdat; sodium gluconate; polarization curve method; electrochemical impedance method; inhibition rate
Abstract

The occurrence of metal corrosion can greatly reduce the air-conditioning efficiency, and even affect the safe and stable operation of equipment in central air-conditioning cooling water circulation system. Adding corrosion inhibitor to cooling water system is currently the most commonly and effective method. Electrochemical impedance method is used to evaluate the corrosion performance of single sodium tungstate, sodium molybdate, and sodium gluconate, while polarization curve method is used to evaluate the corrosion performance of two compound agent. Results show that corrosion performance of sodium tungstate, sodium molybdate, and sodium gluconate is ranged as follows: sodium tungstate > sodium gluconate > sodium molybdate. There has synergistic effect between sodium tungstate and sodium gluconate, as well as between sodium tungstate and sodium molybdate, and mixed use can improve corrosion effect. The optimized prescription is that, the sodium tungstate is 65 mg/L, sodium molybdate is 35 mg/L, by this way, the corrosion rate can reach 98.31%.

Copyright
© 2015, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Download article (PDF)

Volume Title
Proceedings of the 2015 International Conference on Electrical, Automation and Mechanical Engineering
Series
Advances in Engineering Research
Publication Date
July 2015
ISBN
10.2991/eame-15.2015.2
ISSN
2352-5401
DOI
10.2991/eame-15.2015.2How to use a DOI?
Copyright
© 2015, the Authors. Published by Atlantis Press.
Open Access
This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).

Cite this article

TY  - CONF
AU  - M.D. Li
AU  - B. Yang
AU  - J.M. Zhao
AU  - Y.T. Chen
AU  - S.X. Gu
AU  - C.L. Dai
PY  - 2015/07
DA  - 2015/07
TI  - Green Corrosion Inhibitor in Central Air-conditioning Cooling Water
BT  - Proceedings of the 2015 International Conference on Electrical, Automation and Mechanical Engineering
PB  - Atlantis Press
SP  - 4
EP  - 6
SN  - 2352-5401
UR  - https://doi.org/10.2991/eame-15.2015.2
DO  - 10.2991/eame-15.2015.2
ID  - Li2015/07
ER  -