Electromagnetic Transient Simulation of Large Power Transformer Internal Fault
- DOI
- 10.2991/icaees-15.2015.129How to use a DOI?
- Keywords
- parameters of transformer; internal fault; simulation; mathematical model.
- Abstract
In this paper, in the neglect of the core of the magnetic hysteresis, eddy current effect and the core skin effect and based on the analysis and summary of previous experience, an analytical method to determine the parameters of the transformer's turn to turn short circuit fault is improved and perfected in order to determine the parameters of the transformer when the turn-to-turn fault and turn-to-ground fault happens at any position of the transformer. Through the mathematical model of transformer after fault, we can obtain the node voltage equation of the simulation network. And then we adopt three principles to calculate the unknown parameters in the node voltage equation we obtained before. Simulation results verify the effectiveness of the proposed algorithm.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Jun Liu AU - Shiwu Xiao AU - Qingsen Sun AU - Huaxing Wang AU - Lei Yang PY - 2015/07 DA - 2015/07 TI - Electromagnetic Transient Simulation of Large Power Transformer Internal Fault BT - Proceedings of the 3rd International Conference on Advances in Energy and Environmental Science 2015 PB - Atlantis Press SP - 706 EP - 711 SN - 2352-5401 UR - https://doi.org/10.2991/icaees-15.2015.129 DO - 10.2991/icaees-15.2015.129 ID - Liu2015/07 ER -