Analysis and Control Strategy of Scaling Difference of Spray Towers of the Valve Cooling System in Converter Station
- DOI
- 10.2991/iccte-16.2016.218How to use a DOI?
- Keywords
- converter station, valve cooling system, spray tower, scaling difference, improving plan
- Abstract
The valve cooling system of converter station plays a very important role in the DC transmission project, and it is important to keep the system stable running. It is found that great scaling difference appeared among three spray towers of the valve cooling system in Tianshengqiao converter station during overhaul, and this phenomenon seriously affects the stability and effective operation of valve cooling system. Through theoretical analysis and experimental study, this paper reveals the main reason of the scaling difference of the surface of heat exchanger coil, and puts forward the control strategy for the Tianshengqiao converter station. After one year of running, the scaling difference of the surface of heat exchanger coil significantly reduced, and this shows that the effect of improvement is good.
- Copyright
- © 2016, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Shuyong Guo AU - Feng Zheng AU - Qinglin Niu PY - 2016/01 DA - 2016/01 TI - Analysis and Control Strategy of Scaling Difference of Spray Towers of the Valve Cooling System in Converter Station BT - Proceedings of the 2016 International Conference on Civil, Transportation and Environment PB - Atlantis Press SP - 1246 EP - 1252 SN - 2352-5401 UR - https://doi.org/10.2991/iccte-16.2016.218 DO - 10.2991/iccte-16.2016.218 ID - Guo2016/01 ER -