Research on harmonic characteristics of electronic instrument transformer
- DOI
- 10.2991/icmse-15.2015.43How to use a DOI?
- Keywords
- Harmonic; electronic instrument transformer; Harmonic error measurement system
- Abstract
A harmonic error measurement system which can simulate the actual operating conditions of electronic instrument transformer was established for electronic instrument transformer harmonic error measurement. The system consists of High-power current and voltage harmonic source which is used to output fundamental and harmonic signal, harmonic voltage and current standard device and harmonic analyzer. The results indicate that after superposing the fundamental and harmonic, ratio and phase error of electronic current transformer (ECT) becomes larger with increasing frequency; ratio error of electronic voltage transformer(EVT) increases with the increasing harmonics frequency, but EVT phase error changed to negative value at rated current, 150Hz frequency.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Chunyan Yang AU - Haoliang Hu AU - Dengyun Li AU - Qianzhu Xiong AU - Qi Nie AU - Zili Xu AU - Zhongming Wang PY - 2015/12 DA - 2015/12 TI - Research on harmonic characteristics of electronic instrument transformer BT - Proceedings of the 2015 6th International Conference on Manufacturing Science and Engineering PB - Atlantis Press SP - 221 EP - 227 SN - 2352-5401 UR - https://doi.org/10.2991/icmse-15.2015.43 DO - 10.2991/icmse-15.2015.43 ID - Yang2015/12 ER -