Optimal Reactive Power Dispatch Considering Power Loss of Transformer
- DOI
- 10.2991/ifeesm-15.2015.48How to use a DOI?
- Keywords
- distribution network; reactive power optimization; power loss of transformer; differential evolution algorithm
- Abstract
A large proportion of power loss in distribution system is from transformer, which is not considered in the traditional Distribution network Reactive Power Optimization (DRPO). This paper proposes a DRPO model considering the power loss of transformer. The optimization method includes reactive power compensation with capacitor, tap adjusting with On-Load Tap Changer (OLTC) transformer. Simulation on the modified IEEE 33-bus test system with Differential Evolution Algorithm (DEA) is testified, the different load level is also analyzed and compared with the traditional optimization model, the test results show that the DRPO considering power loss of transformer is very necessary for light-loaded system. DRPO considering power loss of transformer is more reasonable and adaptable.
- Copyright
- © 2015, the Authors. Published by Atlantis Press.
- Open Access
- This is an open access article distributed under the CC BY-NC license (http://creativecommons.org/licenses/by-nc/4.0/).
Cite this article
TY - CONF AU - Guo jun An AU - Le er Mao AU - Qiang Yao AU - Chang min Shi PY - 2015/09 DA - 2015/09 TI - Optimal Reactive Power Dispatch Considering Power Loss of Transformer BT - Proceedings of the 2015 International Forum on Energy, Environment Science and Materials PB - Atlantis Press SP - 250 EP - 254 SN - 2352-5401 UR - https://doi.org/10.2991/ifeesm-15.2015.48 DO - 10.2991/ifeesm-15.2015.48 ID - An2015/09 ER -