Analysis of Slope Failure: A Case Study from the Pump House Cut Slope Wall of Lift Irrigation Scheme, Telangana State, India
- DOI
- 10.2991/978-94-6463-258-3_27How to use a DOI?
- Keywords
- Pump House; Wedge Failure; Swedge Software
- Abstract
During the excavation of pump house-II of Kaleshwaram Lift Irrigation Scheme (KLIS) Link-II, sudden slope failure happened on the upstream wall from existing ground level +274.00 to +225.00 m level. In this paper the cause of slope failure at the upstream right-side wall of the pump house and support recommendations for the failure zone are discussed. 126 m long, 50 m wide (including annexure building) and 75.00 m deep, vertical shaft type pump house is being constructed for lifting the 361 cumecs water. Kinematic analysis was carried out to define the shape of the wedge, the orientation of the line of intersection and the direction of sliding. Equal angle projection was used for the analysis. Stability analysis was also done using the stability charts and Swedge RocScience software. The factor of safety (FOS) calculated using the stability chart is 0.44 and using Swedge is 0.4367. Mohr-Coulomb method of failure criterion is used for the analysis. After detailed analysis suitable engineering measures which include rock bolts, grouting and retaining RCC wall were recommended for the stabilization of the wedge portion of the upstream wall of the pump house and the same are being executed at the site.
- Copyright
- © 2023 The Author(s)
- Open Access
- Open Access This chapter is licensed under the terms of the Creative Commons Attribution-NonCommercial 4.0 International License (http://creativecommons.org/licenses/by-nc/4.0/), which permits any noncommercial use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license and indicate if changes were made.
Cite this article
TY - CONF AU - A. K. Naithani AU - D. S. Rawat AU - J. Ramesham AU - Mahesh Babu Tera AU - G. Bramhaiah PY - 2023 DA - 2023/11/08 TI - Analysis of Slope Failure: A Case Study from the Pump House Cut Slope Wall of Lift Irrigation Scheme, Telangana State, India BT - Proceedings of the Rocscience International Conference (RIC 2023) PB - Atlantis Press SP - 257 EP - 263 SN - 2589-4943 UR - https://doi.org/10.2991/978-94-6463-258-3_27 DO - 10.2991/978-94-6463-258-3_27 ID - Naithani2023 ER -